CVE-2026-102073Siemens APOGEE MBC (PPC) (BACnet) integer underflow

SiemensPublished:

CVSS score

8.8

High

CVSS 4.0 from siemens.com

Exploit probability (EPSS)

0.34%

0.34% chance of exploitation in the next 30 days, higher than 28.6% of all CVEs.

CISA KEV

Not in KEV

No confirmed exploitation reported by CISA so far.

Official description

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The affected product web service does not properly validate the length of user-controllable input. This could allow an unauthenticated remote attacker to read portions of device memory or to cause a denial-of-service condition.

Source: NVD · CNA: productcert@siemens.com

How to fix it, step by step

  1. Check whether you're affected

    Find every system running Siemens APOGEE MBC (PPC) (BACnet), Siemens APOGEE MBC (PPC) (P2 Ethernet), Siemens APOGEE MEC (PPC) (BACnet), Siemens APOGEE MEC (PPC) (P2 Ethernet), Siemens APOGEE PXC Compact (BACnet) and compare its version with the affected versions.

  2. Watch for an official fix

    No fix or advisory is listed in the official record yet. Follow the vendor's security announcements; this page updates when one is published.

Was this useful?

How it can be exploited

Attack vector
Network
Attack complexity
Low
Attack requirements
None
Privileges required
None
User interaction
None
Confidentiality
High
Integrity
None
Availability
Low

Values in red make the vulnerability easier to exploit or more damaging. CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Affected products

Affected productsVersions
Siemens APOGEE MBC (PPC) (BACnet)Not specified
Siemens APOGEE MBC (PPC) (P2 Ethernet)Not specified
Siemens APOGEE MEC (PPC) (BACnet)Not specified
Siemens APOGEE MEC (PPC) (P2 Ethernet)Not specified
Siemens APOGEE PXC Compact (BACnet)< V3.5.7
Siemens APOGEE PXC Compact (P2 Ethernet)< V2.8.21
Siemens APOGEE PXC Modular (BACnet)< V3.5.7
Siemens APOGEE PXC Modular (P2 Ethernet)< V2.8.21
Siemens TALON TC Compact (BACnet)< V3.5.7
Siemens TALON TC Modular (BACnet)< V3.5.7

Weakness

Timeline

  1. Published:
  2. Last modified:

Frequently asked questions

Is CVE-2026-102073 being exploited?

There is no confirmed exploitation in CISA's KEV catalog so far. Its EPSS score estimates a 0.3% probability of exploitation in the next 30 days.

What is the CVSS score of CVE-2026-102073?

CVE-2026-102073 has a CVSS 4.0 base score of 8.8 (high).

Which versions are affected?

Siemens APOGEE MBC (PPC) (BACnet), Siemens APOGEE MBC (PPC) (P2 Ethernet), Siemens APOGEE MEC (PPC) (BACnet), Siemens APOGEE MEC (PPC) (P2 Ethernet), Siemens APOGEE PXC Compact (BACnet) (< V3.5.7), Siemens APOGEE PXC Compact (P2 Ethernet) (< V2.8.21)

Is there a patch for CVE-2026-102073?

No patch is linked in the official record yet. Watch the vendor's security advisories.

References

Data: NVD, CVE.org (cvelistV5), CISA KEV and FIRST EPSS. Summary written by RedCVE with AI assistance from the official data.