CVE-2016-8562Siemens SIMATIC CP 1543-1 Improper Privilege Management Vulnerability
CVSS score
7.5
High
CVSS 3.1 from NVD
Exploit probability (EPSS)
3.61%
3.61% chance of exploitation in the next 30 days, higher than 89.8% of all CVEs.
CISA KEV
Actively exploited
Added to KEV on 3 Mar 2022.
US federal deadline to fix: 24 Mar 2022.
Official description
A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Under special conditions it was possible to write SNMP variables on port 161/udp which should be read-only and should only be configured with TIA-Portal. A write to these variables could reduce the availability or cause a denial-of-service.
Source: NVD · CNA: cve@mitre.org
How to fix it, step by step
Treat it as urgent
Attackers are already exploiting this flaw: CISA added it to its Known Exploited Vulnerabilities list on 3 Mar 2022.
US federal agencies must fix it by 24 Mar 2022. It's a sensible deadline for everyone else too.
CISA's full instruction
Apply updates per vendor instructions.
Check whether you're affected
Find every system running Siemens Simatic Cp 1543-1 Firmware, Siemens Siplus Net Cp 1543-1 Firmware and compare its version with the affected versions.
Update to a fixed version
- Update Simatic Cp 1543-1 Firmware, Siplus Net Cp 1543-1 Firmware to 2.0.28 or later.
If you can't update right away
Apply the workaround or mitigation in the vendor's advisory until you can update:
Check for signs of compromise
Updating closes the flaw but doesn't remove an attacker who got in earlier. Review affected systems for unknown accounts, unusual logins and configuration changes, and use any indicators of compromise the vendor or CISA publish.
Confirm the fix
Check that every affected system now reports a fixed version, and recheck the vendor's advisory: fixes are sometimes revised.
Was this useful?
How it can be exploited
- Attack vector
- Network
- Attack complexity
- High
- Privileges required
- Low
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- High
- Availability
- High
Values in red make the vulnerability easier to exploit or more damaging. CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H
Affected products
| Affected products | Versions |
|---|---|
| Siemens Simatic Cp 1543-1 Firmware | < 2.0.28 |
| Siemens Siplus Net Cp 1543-1 Firmware | < 2.0.28 |
Timeline
- Published:
- Added to CISA KEV:
- Last modified:
Frequently asked questions
Is CVE-2016-8562 being exploited?
Yes. CISA added CVE-2016-8562 to its Known Exploited Vulnerabilities catalog on 3 Mar 2022, which means there is evidence of exploitation in the wild. Its EPSS score estimates a 3.6% probability of exploitation in the next 30 days.
What is the CVSS score of CVE-2016-8562?
CVE-2016-8562 has a CVSS 3.1 base score of 7.5 (high).
Which versions are affected?
Siemens Simatic Cp 1543-1 Firmware (< 2.0.28), Siemens Siplus Net Cp 1543-1 Firmware (< 2.0.28)
Is there a patch for CVE-2016-8562?
The official record links to vendor advisories or patches; see “What to do” above.
References
- www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-672373.pdf(Broken Link, Patch, Vendor Advisory)
- cert-portal.siemens.com/productcert/pdf/ssa-672373.pdf(Vendor Advisory)
- www.securityfocus.com/bid/94436(Broken Link, Third Party Advisory, VDB Entry)
- ics-cert.us-cert.gov/advisories/ICSA-16-327-01(Third Party Advisory, US Government Resource)
- www.cisa.gov/known-exploited-vulnerabilities-catalog?field_cve=CVE-2016-8562(US Government Resource)
Data: NVD, CVE.org (cvelistV5), CISA KEV and FIRST EPSS. Summary written by RedCVE with AI assistance from the official data.